− | Correct charge/discharge current: It is recommended never to charge or recharge lead batteries at more than 0.2C, i.e. 20% of the capacity of the battery bank (ex: 20A for a battery bank of 100Ah). | + | *'''Correct charge/discharge current''': '''It is recommended '''never to charge or recharge''' lead batteries at '''more than 0.2C''', i.e. 20% of the capacity of the battery bank (ex: 20A for a battery bank of 100Ah). |
− | + | {{Idea|1=When sizing a photovoltaic installation, make sure that the maximum output current is less than 20% of the battery capacity. Let: Imax (A) = Pmax (W) / Ubat (V) < 0.2C}} <br /> <br /> | |
− | When sizing a photovoltaic installation, make sure that the maximum output current is less than 20% of the battery capacity. Let: Imax (A) = Pmax (W) / Ubat (V) < 0.2C |